Note: Before making any changes please save the original program
backup.
- Go online with the drive->>load drive unit to PG->> Save.
- Go offline- >>Project->> Archive->>Norma-l>>S7 program OK->>Save in Computer Hard disk.
Stationary measurement/Tuning
- Go to SERVO_02->> Commissioning ->>
Stationary/Turning Measurement
- Select Stationary measurement --> Activate measurement
- After Activation you can see this WARNING message and then close this WARNING dialogue box.
- Enable ASSUME CONTROL PRIORITY Option and Accept the Dialogue box.
·
Give the enable commands and then give ON
COMMAND here.
·
After sometime automatically OFF the Machine and
you can see the Status No measurement, then New value in the table, after
ACCEPT the new values to save the new tuned values to the drive.In some cases you must repeat the measurement.
- Copy Ram to ROM for Saving tuning data.
- Load Drive Unit to PG for saving data in your computer Select Drive->>Target Device->>Load drive Unit to PG
Stationary measurement Summary
1.
SERVO_02->> Commissioning ->>
Stationary/Turning Measurement
2.
Select Stationary measurement ->> Activate
measurement
3.
Enable ASSUME CONTROL PRIORITY
->>Enable->>ON->>wait for auto drive Off
4.
Accept new values
5.
Copy Ram to ROM
6.
Load Drive Unit to PG
7.
SAVE project