SINAMICS S210: Reset parameters, the
safety parameters und the Webserver passwords
In order to erase the complete
parameterization including the Safety parameterization and the Webserver
passwords please proceed as follows:
- Create a file with the name “updater.inf” containing the text
“UPDATE_FORMAT_RW 0 1” or download the file from Siemens website. updater.zip (1
KB)
- Copy the file “updater.inf” onto an empty SD-Card (max. 2GB, e.g.
6SL3054-4AG00-2AA0).
- Turn the converter off and insert the SD-Card into the card slot of
the converter.
- Turn the converter back on and wait until the startup of the converter
has completed (RDY LED permanently green).
- Turn the converter off and remove the SD-Card*.
- Turn the converter back on and perform a new parameterization of the
converter – if required – including Safety parameterization and acceptance
test.
Reset the Web server passwords, parameters& safety parameters
|
Important Note: (The SD-Card needs to be removed after erasing the parameters as the converter will go on erasing parameters with every startup when this SD-Card remains in the converter.
When the Card remains in the converter after erasing the parameters and a new parameterization is saved then the converter will start-up with the parameters stored on the SD-Card even though the file “updater.inf” is still present. This parameterization remains active also after removing the card.)
Note:
·
When
erasing the parameters with this SD-Card only the parameterization will be
reset to factory defaults/ delivery state. The installed SINAMICS Runtime
software will be maintained completely therefore a reinstallation is not
required.
·
The
communication settings (IP-Configuration or device name) of the Service
interface (X127) and the PROFINET interface (X150) are not modified by the
erasure process and will be retained!
·
Please
observe that the access to the Webserver is only possible via the Service
interface (X127) after erasing the parametrization. The access via the PROFINET
interface (X150) is only possible after enabling the access in the Webserver
“System -> Settings -> IP-Connections”.