SINAMICS S210: Reset parameters, the safety parameters und the Webserver passwords


SINAMICS S210: Reset parameters, the safety parameters und the Webserver passwords

In order to erase the complete parameterization including the Safety parameterization and the Webserver passwords please proceed as follows:
  • Create a file with the name “updater.inf” containing the text “UPDATE_FORMAT_RW 0 1” or download the file from Siemens website. updater.zip (1 KB) 
  • Copy the file “updater.inf” onto an empty SD-Card (max. 2GB, e.g. 6SL3054-4AG00-2AA0).
  • Turn the converter off and insert the SD-Card into the card slot of the converter.
  • Turn the converter back on and wait until the startup of the converter has completed (RDY LED permanently green).
  • Turn the converter off and remove the SD-Card*.
  • Turn the converter back on and perform a new parameterization of the converter – if required – including Safety parameterization and acceptance test.
Reset the Web server passwords, parameters& safety parameters



Important Note: (The SD-Card needs to be removed after erasing the parameters as the converter will go on erasing parameters with every startup when this SD-Card remains in the converter.
When the Card remains in the converter after erasing the parameters and a new parameterization is saved then the converter will start-up with the parameters stored on the SD-Card even though the file “updater.inf” is still present. This parameterization remains active also after removing the card.)
Note:
·         When erasing the parameters with this SD-Card only the parameterization will be reset to factory defaults/ delivery state. The installed SINAMICS Runtime software will be maintained completely therefore a reinstallation is not required.
·         The communication settings (IP-Configuration or device name) of the Service interface (X127) and the PROFINET interface (X150) are not modified by the erasure process and will be retained!
·         Please observe that the access to the Webserver is only possible via the Service interface (X127) after erasing the parametrization. The access via the PROFINET interface (X150) is only possible after enabling the access in the Webserver “System -> Settings -> IP-Connections”.

Comments

Popular posts from this blog

SINAMICS G120/ S120: Hardware /Software Change ,Project Upload /Download ,Firmware Upgrade

SINAMICS G120/S120 Hardware /Software Change Project Upload /Download Firmware Upgrade Project Upload/ Download by Starter/ Simotion Scout/BOP The following commissioning tools support the commissioning wizard: STARTER Start drive from V13 SP1 IOP from V1.6 and higher BOP2 If a project is already stored on the CF card, use STARTER to upload it to the PC/PG and make a backup copy if necessary. Upload/Download Procedure with STARTER Inverter → PC/PG To back up the settings with STARTER, proceed as follows: Go online:   Click the "load project to PG/PC" button:   or Target Device>> load project to PG/PC button Wait until STARTER reports that data backup has been completed. Save the project: Go offline:    Click Project >>Archive Button. PC/PG → Inverter Normally this option use when you have changes settings offline or you have old project. To load the settings from the PG to th...

SINAMICS S120: Upgrade CU310 to CU310 -2DP_PN

Contents 1.       BACK UP THE EXISTING PROJECT . 2 2.       Upgrade old firmware to new firmware . 2 3.       SWITCH ON THE ELECTRONIC POWER SUPPLY . 3 4.       ESTABLISH THE NETWORK CONNECTION (HARDWARE) 3 5.       CONFIGURE THE NETWORK CONNECTION (SOFTWARE) 3 6.       Download to New Drive . 5 1.     BACK UP THE EXISTING PROJECT If a project is already stored on the CF card, use STARTER to upload it to the PC/PG and make a backup copy if necessary. 2.     Upgrade old firmware to new firmware If the firmware has a new device version you must also select the relevant drive unit in the STARTER project tree and then select the required device version by clicking on menu options Target device >> Device version with the right mouse button: 3.  ...