SINAMICS S120: CU310-2 PN, CU320-2 PN: Maintenance request when allocating Name of Station


Sinamics S120 PN Maintenance request 

when allocating Name of Station

Question

In STEP 7 HW Config, why is a maintenance request signaled at the CU320-2 PN / CU310-2 PN when allocating NameOfStation? The MAINT LED of the CPU lights up yellow.

Answer

Fault status:

In the HW configuration in Step 7, a maintenance request is signaled at the CU320-2 PN/CU310-2 PN.The message (under details for the diagnostics) is as follows:
A Name Of station was already configured/allocated for an additional interface of this module,
which is identical to what was entered for this interface.

Cause of the error:

CU3x0-2 PN modules have an IE and a PN interface.
Not only must the addresses of the IE (X127) and the PN interface (X150) be different.
Also, the name of the X127 (r8910) must be different than the name of the X150 (r8930).

Remedy:

Establish a connection to the interface X127 of the CU, and allocate a different name.

Note:



In this particular case, a multi-interface error is signaled in the TIA Portal.

Comments

Popular posts from this blog

SINAMICS G120/ S120: Hardware /Software Change ,Project Upload /Download ,Firmware Upgrade

SINAMICS G120/S120 Hardware /Software Change Project Upload /Download Firmware Upgrade Project Upload/ Download by Starter/ Simotion Scout/BOP The following commissioning tools support the commissioning wizard: STARTER Start drive from V13 SP1 IOP from V1.6 and higher BOP2 If a project is already stored on the CF card, use STARTER to upload it to the PC/PG and make a backup copy if necessary. Upload/Download Procedure with STARTER Inverter → PC/PG To back up the settings with STARTER, proceed as follows: Go online:   Click the "load project to PG/PC" button:   or Target Device>> load project to PG/PC button Wait until STARTER reports that data backup has been completed. Save the project: Go offline:    Click Project >>Archive Button. PC/PG → Inverter Normally this option use when you have changes settings offline or you have old project. To load the settings from the PG to th...

Sinamics S120: HOMING(Absolute Encoder Adjustment)

Homing HOMING (Absolute Encoder Adjustment) Note: Doing this process will make your actual position as home position make sure your machine is at home position or beware of mechanical position. ·          Select SERVO_02 -> Technology -> Basic Positioner --> Homing -> Homing/configuration (right side window) -> Homing. ·          Before doing homing your actual value will be different. ·          Click Perform absolute value calibration (Before doing this make machine position in home position, then make homing) ·          After done Homing, it will ask to save the value (Copy RAM TO ROM). And actual value will go 0 value. ·          You can see this when doing RAM TO ROM option. Saving all the data in the Permanent memory. ·    ...

SINAMICS S210: Reset parameters, the safety parameters und the Webserver passwords

SINAMICS S210: Reset parameters, the safety parameters und the Webserver passwords In order to erase the complete parameterization including the Safety parameterization and the Webserver passwords please proceed as follows: Create a file with the name “updater.inf” containing the text “UPDATE_FORMAT_RW 0 1” or download the file from Siemens website. updater.zip (1 KB)  Copy the file “updater.inf” onto an empty SD-Card (max. 2GB, e.g. 6SL3054-4AG00-2AA0). Turn the converter off and insert the SD-Card into the card slot of the converter. Turn the converter back on and wait until the startup of the converter has completed (RDY LED permanently green). Turn the converter off and remove the SD-Card*. Turn the converter back on and perform a new parameterization of the converter – if required – including Safety parameterization and acceptance test. Reset the  Web server passwords,  parameters&  safety parameters ...