Skip to main content

SINAMICS S120: CU310-2 PN, CU320-2 PN: Maintenance request when allocating Name of Station


Sinamics S120 PN Maintenance request 

when allocating Name of Station

Question

In STEP 7 HW Config, why is a maintenance request signaled at the CU320-2 PN / CU310-2 PN when allocating NameOfStation? The MAINT LED of the CPU lights up yellow.

Answer

Fault status:

In the HW configuration in Step 7, a maintenance request is signaled at the CU320-2 PN/CU310-2 PN.The message (under details for the diagnostics) is as follows:
A Name Of station was already configured/allocated for an additional interface of this module,
which is identical to what was entered for this interface.

Cause of the error:

CU3x0-2 PN modules have an IE and a PN interface.
Not only must the addresses of the IE (X127) and the PN interface (X150) be different.
Also, the name of the X127 (r8910) must be different than the name of the X150 (r8930).

Remedy:

Establish a connection to the interface X127 of the CU, and allocate a different name.

Note:



In this particular case, a multi-interface error is signaled in the TIA Portal.

Comments

Popular posts from this blog

SINAMICS G120/ S120: Hardware /Software Change ,Project Upload /Download ,Firmware Upgrade

SINAMICS G120/S120 Hardware /Software Change Project Upload /Download Firmware Upgrade Project Upload/ Download by Starter/ Simotion Scout/BOP The following commissioning tools support the commissioning wizard: STARTER Start drive from V13 SP1 IOP from V1.6 and higher BOP2 If a project is already stored on the CF card, use STARTER to upload it to the PC/PG and make a backup copy if necessary. Upload/Download Procedure with STARTER Inverter → PC/PG To back up the settings with STARTER, proceed as follows: Go online:   Click the "load project to PG/PC" button:   or Target Device>> load project to PG/PC button Wait until STARTER reports that data backup has been completed. Save the project: Go offline:    Click Project >>Archive Button. PC/PG → Inverter Normally this option use when you have changes settings offline or you have old project. To load the settings from the PG to th...

SINAMICS S120: Upgrade CU310 to CU310 -2DP_PN

Contents 1.       BACK UP THE EXISTING PROJECT . 2 2.       Upgrade old firmware to new firmware . 2 3.       SWITCH ON THE ELECTRONIC POWER SUPPLY . 3 4.       ESTABLISH THE NETWORK CONNECTION (HARDWARE) 3 5.       CONFIGURE THE NETWORK CONNECTION (SOFTWARE) 3 6.       Download to New Drive . 5 1.     BACK UP THE EXISTING PROJECT If a project is already stored on the CF card, use STARTER to upload it to the PC/PG and make a backup copy if necessary. 2.     Upgrade old firmware to new firmware If the firmware has a new device version you must also select the relevant drive unit in the STARTER project tree and then select the required device version by clicking on menu options Target device >> Device version with the right mouse button: 3.  ...

SINAMICS S120: Automatic Speed Controller Setting/ Servo Tuning

Automatic Speed Controller Setting/ Servo Tuning ·          In SCOUT/STARTER, press the button     to start the automatic controller setting. ·          Go to SERVO_02->> Commissioning ->> automatic controller setting ·          In TIA Portal/Start drive go to the window "Commissioning" -> "Automatic Servo Tuning". ·          Select Drive Unit (2)->>Select Speed Controller ·          Select drive (5)->>Assume control Priority ·          ON the drive ->>Select perform all step ·          Wait for all step to finish. The determined settings of the speed controller have to be accepted before they ta...